Fact - System Data -
S7-200
|
|
Identical technical specifications of the CPUs 221, 222, 224, 224 XP, 226 |
Feature |
CPUs 221, 222, 224, 224 XP, 226 |
32-bit floating-point arithemetic in accordance with IEEE
norm |
Yes |
Fully configurable, integrated PID controller |
Yes, up to 8 independent PID controllers |
Bit processing speed |
0.22μs |
Time-controlled interrupts |
2 (cycle time between 1 and 255 ms at 1 ms resolution) |
Hardware interrupts (edge detection at inputs) |
Max. 4 inputs |
Flag, timers, conuters |
256 each |
High-speed counters |
4-6 (depending on CPU), max.30 kHz, or 200 kHz with CPU
224 XP |
Pulse outputs (pulse-width-or frequency-modulated) |
2 outputs, 20 kHz each (for DC versions), 100 kHz with CPU
224 XP |
Program and data memory |
Retentive (non-volatile) |
Storage of dyn. data in the event of a power failure |
Retentive : Non-volatile via internal high-performance capacitor
and / or additional battery module : loading of data lock with
STEP7-Micro/WIN TD 200C or by user program ot integrated
EEPROM |
Buffering of the dynamic data with battery module |
Type. 200 days |
Integrated communications interface |
Yes, RS 485 interface uspporing the following operating
modes : PPI master or Slave / MPL slave / Freeport (freely configurable ASCII protocol) |
Max. baud rate |
187.5 kbaud (PP/MPI) or 115.2 kbaud (freeport) |
Progamming software |
STEP 7-Micro/WIN supports all standards such as STL, CSF, CSF or LAD |
Optional program memory module |
Yes, programmable in CPU, for program transmission, data logging. recipe, documentation |
DC/DC/DC version |
Yes |
Supply voltage |
24 V DC |
Digital inputs |
24 V DC |
Digital outputs |
24 V DC. max 0.75 A, parallet connection possible of higher switching capacity |
AC/DC/realy version |
Yes |
Supply voltage |
85-264 V AC |
Digital inputs |
24 V DC |
Digital outputs |
5-30 V DC or 5-250 V AC, max. 2 A (relay) |
|
|
Specific technical data on the CPUs |
Feature |
221 |
222 |
224 |
224 XP |
226 |
|
|
|
|
|
|
Integrated dig. inputs/outputs |
6 DI/4 DO |
8 DI/6 DO |
14 DI/ 8 DO |
14 DI/10 DO |
24 DI/16 DO |
Digital inputs/outputs/max.
number of channels with
expansion modules |
- |
40/38/78 |
94/82/168 |
94/82/168 |
128/120/248 |
Analog inputs/outputs/max.
number of channel with
expansion modules |
- |
8/4/10 |
28/14/35 |
2 AI/1 AO integrated 30/15/38 |
28/14/35 |
Program memory |
4 KB |
4 KB |
8/12 KB |
12/16 KB |
16/24 KB |
Data memory |
2 KB |
2 KB |
8 KB |
10 KB |
10 KB |
Storage of dyn. data via high- performance capacitor |
Type. 50 h |
Type. 50 h |
Type. 100 h |
Type. 100 h |
Type. 100 h |
High-speed counters |
4x30 kHz, of which 2x20 kHz
A/B counter usable
|
4x30 kHz, of which 2x20 kHz
A/B counter usable |
6x30 kHz, of which 4x20 kHz
A/B counter usable |
6x30 kHz, of which 3x20 kHz+100 kHz
A/B counter usable |
6x30 kHz, of which 4x20 kHz+100 kHz
A/B counter usable |
Communications interfaces
RS
485 |
1 |
1 |
1 |
2 |
2 |
Supported protocols
-PPI master/slave
-MPI slave
-Freeport
(freely config. ASCII protocol) |
Yes
Yes
Yes |
Yes
Yes
Yes |
Yes
Yes
Yes |
Both interfaces
Yes
Yes
Yes |
Both interfaces
Yes
Yes
Yes |
Optional communications possibilities |
Not expandable |
Yes, PROFIBUS DP Slave
and / or AS-Interface Master / Ethermet
/ Internet / Modem |
Yes, PROFIBUS DP Slave
and/or AS-Interface Master / Ethermet
/ Internet / Modem |
Yes, PROFIBUS DP Slave
and/or AS-Interface Master / Ethermet
/ Internet / Modem |
Yes, PROFIBUS DP Slave
and/or AS- Interface Master / Ethermet /
Internet/ Modem |
Integrated 8 bit analog
potentiometer
(for commissiong, value change) |
1 |
1 |
1 |
2 |
2 |
Real-time clock |
Optional |
Optional |
Yes |
Yes |
Yes |
Integrated 24-V-DC sensor
supply volt. |
Max. 180 mA |
Max. 180 mA |
Max. 280 mA |
Max. 280 mA |
Max. 400 mA |
Removable terminal strip |
- |
- |
Yes |
Yes |
Yes |
Dimension (W x H x D in mm) |
90 x 90 x 62 |
90 x 90 x 62 |
120.5 x 80 x 62 |
140 x 80 x 62 |
196 x 80 x 62 |
|
|
|
|
|
Technical data |
Digital I/O modules |
EM 221 |
EM 222 |
EM 222 |
Number of inputs / outputs |
8 DI (DC) |
8 DO (DC) |
8 DO (realy) |
Number of inputs |
8 |
- |
- |
Input type |
24 V DC |
- |
- |
Sinking / Sourcing |
x / x |
- |
- |
Input voltage |
24 V DC, max, 30 V |
- |
- |
Isolation |
Yes |
- |
- |
In group of |
4 inputs |
- |
- |
Number of outputs |
- |
8 |
8 |
Output type |
- |
24 V DC |
realy |
Output current |
- |
0.75 A in group-parallet connection possible for higher switching capacity |
2 A |
Output voltage DC |
- |
20.4-28.8 V |
5-30 V |
(premissible range) AC |
- |
- |
5-250 V |
Isolation |
- |
Yes |
Yes |
In groups of |
- |
4 outputs |
4 outputs |
Removable terminal strip |
Yes |
Yes |
Yes |
Dimensions (W x H x D in mm) |
46 x 80 x 62 |
46 x 80 x 62 |
46 x 80 x 62 |
|
|
S Digital I/O modules |
EM 221 |
EM 222 |
EM 222 |
Number of inputs / outputs |
16 DI (DC) |
4 DO (DC) |
4 DO (realy) |
Number of inputs |
16 |
- |
- |
Input type |
24 V DC |
- |
- |
Sinking / Sourcing |
x / x |
- |
- |
Input voltage |
24 V DC, max, 30 V |
- |
- |
Isolation |
Yes |
- |
- |
In group of |
4 inputs |
- |
- |
Number of outputs |
- |
4 |
4 |
Output type |
- |
24 V DC |
realy |
Output current |
- |
5 A max. per output, switchable in parallet for greater power |
10 A max. per output |
Output voltage DC (permissible range) AC |
- |
20.4-28.8 V |
12-250 V |
Isolation |
- |
Yes |
Yes |
In groups of |
- |
1 outputs |
1 outputs |
Removable terminal strip |
Yes |
Yes |
Yes |
Dimensions (W x H x D in mm) |
17.2 x 80 x 62 |
46 x 80 x 62 |
46 x 80 x 62 |
|
|
Accessories |
RS 232 Smart Cable (Multimaster1,2) |
USB Smart Cable (Multimaster3) |
Isolation |
Yes |
Yes |
Power supply |
From CPU |
From USB Port |
Supported protocols |
PPI and ASCII (Freeport); 10/11bit |
PPI; 10/11 bit |
PPI communication |
9.6 k; 19.2 k; 187.5 k |
9.6 k; 19.2 k: 187.5 k |
Communication setting |
DIP switch: RS 232 automatically |
unnecessary |
LED display |
Yes |
Yes |
Required software |
STEP 7-Micro/Win V3.2 from SP4 |
STEP 7-Micro/Win V3.2 from SP4 |
|
|
Technical Data |
Digital I/O modules |
EM 223 |
EM 223 |
EM 223 |
EM 223 |
EM 223 |
EM 223 |
Number of inputs/outputs |
4 DI(DC)
4 DO (DC) |
4 DI(DC)
4 DO (realy) |
8 DI (DC) &
8 DO (DC) |
8 DI (DC) &
8 DO (realy) |
16 DI (DC) &
16 DO (DC) |
16 DI (DC) &
6 DO (realy) |
Number of inputs |
4 |
4 |
8 |
8 |
16 |
16 |
input type |
24 V DC |
24 V DC |
24 V DC |
24 V DC |
24 V DC |
24 V DC |
Sinking / Sourcing |
x / x |
x / x |
x / x |
x / x |
x / x |
x / x |
Input voltage |
24 V DC,
max, 30 V |
24 V DC,
max, 30 V |
24 V DC,
max, 30 V |
24 V DC,
max, 30 V |
24 V DC,
max, 30 V |
24 V DC,
max, 30 V |
Isolation on groups of |
No
- |
No
- |
Yes
4 inputs |
Yes
4 inputs |
Yes
8 inputs |
Yes
8 inputs |
Number of Outputs |
4 |
4 |
8 |
8 |
16 |
16 |
Output type |
24 V DC |
Realy |
24 V DC |
Realy |
24 V DC |
Realy |
Output current |
0.75 A in Parallel connection possible of higher switching capacity |
2 A |
0.75 A in group Parallel connection possible of higher switching capacity |
2 A |
0.75 A in group Parallel connection possible of higher witching capacity |
2 A |
Out Voltage DC |
20.4-28.8 V |
5-30 V |
20.4-28.8 V |
5-30 V |
20.4-28.8 V |
5-30 V |
(Permissible range) AC |
- |
5-250 V |
- |
5-250 V |
- |
5-250 V |
Isolation |
No |
No |
Yes |
Yes |
Yes |
Yes |
In group of |
- |
- |
4 outputs |
4 outputs |
4/4/8 outputs |
4 outputs |
Removable terminal strip |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Dimension (W x H x D in mm) |
46 x 80 x 62 |
46 x 80 x 62 |
71.2 x 80 x 62 |
71.2 x 80 x 62 |
137.3 x 80 x 62 |
137.3 x 80 x 62 |
|
|
Digital I/O modules |
EM 231 |
EM 232 |
EM 235 |
Number of inputs / outputs |
4 Al |
2 AO |
4 Al & 1 AO |
Number of inputs |
4 |
- |
4 |
Input type |
0-10 V/0-20 mA |
- |
0-10 V/0-20 mA |
Voltage ranges |
0-10 V, 0-5 V
+/-5 V, +/-2.5 V |
- |
0-10 V, 0-5 V
+/-5 V, +/-2.5 V and others |
Resolution |
12 bit |
- |
12 bit |
Isolation |
No |
- |
No |
Number of outputs |
- |
2 |
1 |
Output Types |
- |
+/-10 V, 0-20 mA |
+/-10 V, 0-20 mA |
Resolution |
-
11 bit current |
12 bit volt.,
11 bit current |
12 bit volt. |
Isolation |
- |
No |
No |
Removable terminal strip |
No |
No |
No |
Dimensions (W x H x D in mm) |
17.2 x 80 x 62 |
46 x 80 x 62 |
17.2 x 80 x 62 |
|
|
|
|
|
Technical data |
Temperature measurement modules |
EM 231 TC thermocoupes |
EM 231 RTD resistance-type sensors |
Number of inputs / outputs |
4 AI |
2 AI |
Number of inputs |
4 |
2 |
Input type |
Thermocouples
Type S, T, R, E, N, K, J
Voltage+/-80 mV |
Pt 100, 200, 500, 1000 ohm,
Pt 10.000,
Ni 10, 120, 1000 ohm,
R 15, 300, 600 ohm |
Resolution |
15 bit + sign |
15 bit + sign |
Isolation |
500 V AC |
500 V AC |
Cold-junction compensation |
Yes |
Not nec. |
Wiring |
Two-wire |
Two-, three-or-four-wire |
Max. wire length to sensor |
100 m |
100 m |
Removable terminal strip |
No |
No |
Dimensions (W x H x D in mm) |
71.2 x 80 x 62 |
71.2 x 80 x 62 |
|
|
Temperature values in Centigrade of degree Fahrenheit are available in the program as values with on decimal place. |
|
|
Positioning module EM 253 |
|
Number of inputs |
5 points |
Type of inputs |
Active high / active low (IEC Type 1 sink, except ZP) |
Number of integrated outputs |
6 points (4signals) |
Type of outputs
P0+, P0-, P1+, P1-
P0, P1+, DIS, CLR |
RS-422 driver
Open drain
|
Switching frequency
P0+, P0-, P1+, P1- |
200 kHz |
Power supply
L+ supply voltage
Logic output voltage
L + supply current VS, 5 V DC load
Load current
0 mA (No load)
200 mA (rated load) |
11 to 30 V DC
+5 V DC +/-10 %, max. 200 mA
12-V-DC input 24-V-DC input
120 mA 70 mA
300 mA 130 mA |
Dimensions (W x H x D) |
71.2 x 80 x 62 |
Weight |
0.190 kg |
Dissipation |
2.2 W |
V-DC requirements
+5 V DC
+24 V DC |
190 mA
70 mA
|
|
|
|
|
|
Technical data |
SIWAREX MS |
|
Communication interfaces |
SIMATIC S7 bus, RS 232, TTY |
Measuring properties
• Fault limit acc. to DIN 1319-1 of the measuring range
end value at 200±10 K
• Internal resolution
data format of weight values |
0.05%
65.535
2 byte (fixed point)
|
Number of measurements / second |
50 or 30 |
Load cells |
DMS in 4-order 6- conductor technology |
Load cell identier |
1 mV/V up to 4mV/V |
Max. distance of load cells |
500 m |
Ex approvals and safety |
CE, ATEX 100, FM, UL, cULus Haz.Loc. (all in preparation) |
Degree of protection acc. to DIN EN 60529; IEC 6059 |
IP 20 |
|
|
|
|
|
Technical Data |
Operator panels |
TD 100C |
TD 200 |
TD 200C |
OP 73micro |
TP 177micro |
Display |
|
LC -Display |
LC-Display |
|
LC-Display 5.7", STN, |
Number of lines |
4 |
2 |
2 |
- |
- |
Characters per line (max.) |
10/16 (ASCII/Cyrillic
8 (chinese) |
20 (ASCll/Cyrillic), 10 (Chinese) |
20 (ASCll/Cyrillic), 10 (Chinese) |
- |
- |
Character height |
3.34 mn |
5 mn |
5 mn |
- |
- |
Resolution |
- |
- |
- |
160 x 48 pixels |
320 x 240 pixels
(240 x 320 for
veritcal configuration of TP 177 micro |
Operator Controls |
Membrane keyboard |
Membrane keyboard |
Membrane keyboard |
Membrane keyboard |
Touch Screen |
Function keys (programmable) |
14 user- configurable |
8 |
20 freely configurable |
4 |
- |
System keys |
- |
5 |
24 V DC |
8 |
- |
Memory integrated
(usable memory for
user data) |
User data on CPU |
User data on CPU |
User data on CPU |
128 KB Flash |
256 KB Flash |
Interfaces |
1 PPI (RS 485); for setup of a network with max. 126 nodes |
1 PPI (RS 485); for setup of a network with max. 126 nodes |
1 PPI (RS 485); for setup of a network with max. 126 nodes |
1 x RS 485 |
1 x RS 485 |
Functinality |
|
|
|
|
|
Signals
(freely defineble signal classes) |
40 |
80 |
80 |
250 |
500 |
Signal buffer (number of entries) |
- |
- |
- |
128
(no battery backup |
128
(no battery backup |
Mimic diagrams |
32 |
64 |
64 |
250 |
250 |
Variables |
208 |
864 |
864 |
500 |
250 |
Graphic objects |
- |
- |
Icons |
Bitmaps/icons
/background images |
Bitmaps/icons/
background images |
Numerical / alphabetic input |
• /- |
• /- |
• /- |
• / • |
• / • |
Password |
• |
• |
• |
• |
• |
Online languages |
1 |
5 |
5 |
5 |
5 |
Bar charts
(pixel graphics) |
• |
• |
• |
• |
• |
Degree of protection
(front / rear) |
IP65, IP20 |
IP65, IP20 |
IP65, NEMA4 / IP20 |
IP65, ( When built in, NEMA4 / NEMA4X, NEMA12 / IP20 |
IP65, ( When built in, NEMA4 / NEMA4X,
NEMA12 / IP20 |
Dimensions |
|
|
|
|
|
Front panel W x H in mm |
90 x 76 |
148 x 76 |
148 x 76 |
154 x 84 |
212 x 156 |
Depth of device in mm |
36 (max. 44 with fittings) |
27 |
27 |
27 |
42 |
Certification |
CE, cULus, FM, C- Tick, ATEX |
CE, cULus, FM, C-Tick, ATEX |
CE, cULus, FM, C-Tick, ATEX |
In prep, FM, cULus,
CE, C-Tick, |
In prep, FM, cULus,
CE, C-Tick, |
Supply voltage |
24 V DC
(from S7-200) |
24 V DC |
24 V DC |
24 V DC |
24 V DC |
Ambient conditions
Operating temperature
• Vertical mounting
• Max. angle of inclination
Transort / storage temperature |
0 0C to 60 0C
0 0C to 60 0C
-20 0C to 70 0C |
0 0C to 60 0C
0 0C to 60 0C
-20 0C to 70 0C
|
0 0C to 60 0C
0 0C to 60 0C
-20 0C to 70 0C
|
0 0C to 50 0C
0 0C to 40 0C
-20 0C to 70 0C
|
0 0C to 50 0C
0 0C to 40 0C
-20 0C to 60 0C
|
Weight |
0.26 lb |
0.42 lb |
0.44 lb |
0.66 lb |
1.54 lb |
Configuration / programming |
Micro / WIN 4.0 SP |
Micro / WIN 4.0 |
Micro / WIN 4.0 |
From WinCC flexible Micro |
From WinCC flexible Micro |
|
|
|
|
|
Technical data |
Communications module |
EM 277 PROFIBUS DP module |
CP 243-2 AS-i master module |
Inteface |
1 communications interface RS 485 |
AS-Interface |
Supported protocols : |
- MPI slave
- PROFIBUS DP slave |
AS-Interface |
Transmission rate |
9,600 baud up to 12 Mbaud adaptive |
- Max. 5 ms cycle time with 31 slaves
- Max. 10 ms cycle time with 62 slaves |
Connectable stations : |
- Text display TD 200, V2.0 or later
- Operator panels, touch panels
- PG / PC with MPI interface (CPU download / status via Micro / WIN possible)
- CPU S7-300 / 400
- PROFIBUS DP master or slaves |
Max. 62 AS-Interface slaves |
Status display |
CPU error, power, DP error, DX mode |
Status display for slaves, error displays |
Station address |
Adjustable on module |
Not necessary |
Galvanic Isolation |
500 V AC |
No |
Max. cable length (without repeater) |
1200 m (at 93,75 kbaud) |
100 m |
Removable terminal strip |
No |
Yes |
Dimensions (W x H x D in mm) |
71 x 80 x 62 |
71.2 x 80 x 62 |
Weight in g |
175 |
210 |
Dissipation in W |
2.5 |
1.8 |
|
|
Modem communication modules |
EM 241 modem module |
SINAUT MD 720-31 |
Phone connection : |
|
GPRS / GSM modem |
Isolation (Phone line against logic and...) |
1500 V AC (galvanic) |
- |
Cable connector |
RJ11 (6 points, 4-wire) |
SMA / 50 ohm (antenna) RS 232, jack : D-sub 9-pin |
Modem standards |
Bell 103, Bell 212, V..21, V.22, V.22 bis,
V.23c, V.32, V.32 bis, V.34 (standard) |
GPRS / CSD / quadband 850 / 900 / 1900 MHz
V.24 / V.28 (standard) |
Safety features |
Password, callback |
- |
Calling method |
Pluse or tone dialing |
- |
Messaging protocols (SMS) |
Numerical
TAP (alphaanumeric)
UCP commands 1, 30, 51 |
SMS / AT commands
- |
Industrial standard protocols |
Mode RTU, PPI, integrated functions for data exchange
|
- |
Dimensions (W x H x D) |
71.2 x 80 x 62 |
114 mm x 22.5 mm x 99 mm |
Weight |
0.190 kg |
0.150 kg |
Dissipation |
2.1 W |
5.5 W |
V-DC requirements
+ 5 V DC
+ 24 V DC |
80 mA
70 mA
|
12-30 V DC (24 V DC nominal) |
|
|
Modem communication modules |
CP 243-1 |
CP 243-1 IT |
Transmission rate |
10 / 100 Mbits |
10 / 100 Mbits |
Interface (connection industrial Ethernet) |
RJ45 |
RJ45 |
Supply voltage |
24 V DC |
24 V DC |
Power consumption via backplane /
via 24 V DC external |
55 mA / 60 mA |
55 mA / 60 mA |
Dissipation 24 V DC |
1.75 W |
1.75 W |
Dimensions (W x H x D) |
71.2 x 80 x 62 |
71.2 x 80 x 62 |
Weight |
150 kg |
150 kg |
S7 / PG communication |
|
|
Number of operable connections |
8 S7 connections + 1 PG connection |
8 S7 connections + 1 PG connection |
Configuration |
With STEP 7-Micro/WIN (V3.2 SP1 or later) |
With STEP 7-Micro/WIN
(
V3.2 SP3 or later) |
IT communications |
|
|
Number of FTP / HTTP connections to
E-mail server |
- |
1 |
E-mail clients |
- |
32 E-mail with max. 1024 characters |
Number of FTP / connections |
- |
1/4 |
Ajustables access protection |
- |
8 users |
Memory capacity of the file system |
- |
8 Mbyte |
|
|
Product |
Order No. |
CPUs |
|
CPU 221 DC/DC/DC (not expandable) |
6ES7 211-0AA23-0XB0 |
CPU 221 AC/DC/realy (not expandable) |
6ES7 211-0BA23-0XB0 |
CPU 222 DC/DC/DC |
6ES7 212-1AB23-0XBO |
CPU 222 AC/DC/realy |
6ES7 212-1BB23-0XB0 |
CPU 224 DC/DC/DC |
6ES7 214-1AD23-0XB0 |
CPU 224 AC/DC/realy |
6ES7 214-1BD23-0XB0 |
CPU 224XP DC/DC/DC |
6ES7 214-2AD23-0XB0 |
CPU 224XP AC/DC/realy |
6ES7 214-2BD23-0XB0 |
CPU 226 DC/DC/DC |
6ES7 216-2AD23-0XB0 |
CPU 226 AC/DC/realy |
6ES7 216-2BD23-0XB0 |
|
Expansion modules |
|
Digital and analog expansions |
|
Inputs module 8 x DI 24 V DC |
6ES7 221-1BF22-0XA0 |
Inputs module 8 x DI 120 / 230 V |
6ES7 221-1EF22-0XA0 |
Inputs module 16 x DI 24 V DC |
6ES7 221-1BH22-0XA0 |
Inputs module 8 x DO 24 V DC |
6ES7 222-1BF22-0XA0 |
Inputs module 8 x DO realy |
6ES7 222-1HF22-0XA0 |
Inputs module 8 x DO 120 / 230 V |
6ES7 222-1EF22-0XA0 |
Inputs module 4 x DO 24 V DC 5 A |
6ES7 222-1BD22-0XA0 |
Inputs module 4 x DO realy 10 A |
6ES7 222-1HD22-0XA0 |
Inputs module 4 x DI 24 V DC / 4 x DO 24 V DC |
6ES7 223-1BF22-0XA0 |
Inputs module 4 x DI 24 V DC / 4 x DO realy |
6ES7 223-1HF22-0XA0 |
Inputs module 8 x DI 24 V DC / 8 x DO 24 V DC |
6ES7 223-1BH22-0XA0 |
Inputs module 8 x DI 24 V DC / 8 x DO realy |
6ES7 223-1PH22-0XA0 |
Inputs module 16 x DI 24 V DC / 16 x DO 24 V DC |
6ES7 223-1BL22-0XA0 |
Inputs module 16 x DI 24 V DC / 16 x DO realy |
6ES7 223-1PL22-0XA0 |
Analog input module 4 AI 12 bit |
6ES7 231-0HC22-0XA0 |
Analog input / output module 4 AI / 1 AO 12 bit |
6ES7 235-0KD22-0XA0 |
Analog output module 2 AO 12 bit |
6ES7 232-0HB22-0XA0 |
|
Specific expansions |
|
Analog input module RTD, 2 AI, PT100 / 200 / 500 / 1000, Ni100 / 120 / 1000, Cu10,
resist. 150 / 300 / 600 ohm, 16 bit |
6ES7 231-7PB22-0XA0 |
Analog input module TC, 4 AI, ±80 mV and Theromcouples, type J, K, S, T, R, E, N, 16 bit |
6ES7 231-7PD22-0XA0 |
Positioning expansion module (EM)1), 200 kHz, for controlling stepper motors or
servo drives, open-loop control, parameterization via Micro/WIN |
6ES7 231-1AA22-0XA0 |
SIWAREX MS Micro Scale Weighing module |
7MH4930-0AA01 |
|
Communication |
|
PROFIBUS DP module EM 2771) |
6ES7 277-0AA22-0XA0 |
AS-Interface master module CP 243-2 |
6GK7 243-2AX01-0XA0 |
Modem EM1), modem expansion module for analog telephone network for remote
control centers, signaling, CPU-to-PC communication |
6ES7 241-1AA22-0XA0 |
Industrial Etherent CP 243-1, S7-200 interface to industrial Ethernet |
6GK7 243-1EX00-0XE0 |
Industrial Etherent CP 243-1-IT; function same as CP 243- in addition: FTP, e-mail, HTML |
6GK7 243-1GX00-0XE0 |
GPRS modem SINAUT MD 7203 |
6NH9720-3AA00 |
Anternna ANT 794-4-4 MR |
6NH9860-1AA00 |
|
Manuals |
|
|
|
Op 73micro / TP 177micro operating instructions |
6AV6 691-ADF01-0AB0 |
User manual, WinCC flexible Micro
|
|
CP 243-2 communications processor manual |
6GK7 243-2AX00-8BA0 |
|
|
Product |
Order No. |
HMI |
|
TD 100C text display with individual user interface 4-line, and fitting accessories,
187.5 kbaud |
6ES7 272-1BA10-0YA0 |
TD 100C text display, 2-lines with cable (2.5 M) and fitting accessories, 187.5 kbaud |
6ES7 272-0AA30-0YA0 |
TD 200C text display with individual user interface, 2-lines, with cable (2.5m) and
fitting accessories, 187.5 kbaud |
6ES7 272-1AA10-0YA0 |
OP 73micro, operator panel, pixel graphics 3" display, configurable with WinCC
flexibleMicro |
6AV6 640-0BA11-0AAX0 |
TP 177micro, touch panel, pixel graphics 5.7" display, configurable with WinCC
flexible Micro |
6AV6 640-0CA11-0AAX0 |
|
Accessories |
|
Battery module |
6ES7 291-8BA20-0XA0 |
EEPROM memory module (up to CPU...22 0XB0)
|
|
Data logger cartridge, 64 KB (from CPU... 23 0XB0) |
6ES7 291-8GF23-0XA0 |
Data logger cartridge, 256 KB (from CPU... 23 0XB0)
|
|
Clock module, incl. battery (221, 222 to... 22 0XB0) |
6ES7 297-1AA20-0XA0 |
Clock module, incl. battery (221, 222 to... 23 0XB0)
|
|
Extension cable for expansion module, 0.8 m |
6ES7 290-6AA20-0XA0 |
PC / PPI cable, RS 232 / 485 cable for PC / laptop / modem / xxx
to s7- 200,max. 187.5 kbits / s, Multimasters, ASCII, Freeport
|
|
PC / PPI cable, USB / 485 cable for PC / laptop to S7-200, max. 187.5 kbit/s, Multimaster |
6ES7 901-3DB30-0XA0 |
|
|
TD 100C connecting cable to CPU |
6ES7 901-3EB10-0XA0 |
CP5511 : PCMCIA, Type II, RS 485 (PPI / MP / PROFIBUS) for PC / laptop with max.
12 Mbit / s
|
|
CP5611 : PCI card, RS 485 (PPI / MP / PROFIBUS) for PC / laptop with max. 12 Mbit / s |
6GK1 561-1AA00 |
Power supply unit, SITOP power 24 V / 3.5 A
|
|
Blank templete sheets for the front the panel of the TD 100C
(DIN A4, 10 sheets, each with 6 temples, perforated) |
6ES7 272-BF00 7AA0 |
Blank templete sheets for the front the panel of the TD 200C
(DIN A4, 10 sheets, each with 3 temples, perforated)
|
|
SIWATOOL connecting cable between SIWAREX MS and PC |
7MH4 702-8CA |
Grounding terminal for MS module, 10 pcs. / unit
|
|
|
Software |
|
STEP 7-Micro / WIN programming software, V4 for Win 2000, XP, 5 languages, incl.
documentation on CD; single-user license |
6ES7 810-2CCO3-0YX0 |
STEP 7-Micro / WIN programming software, V4 for Win 2000, XP, 5 languages, incl.
documentation on CD; upgrade from Micro / DOS and Micro / WIN Vx.x to V4 |
6ES7 810-2CC03-0YX3 |
STEP 7-Micro / WIN add-on Instruction library V.1.1, control of drives
(USS protocol) and data transmission via Modbus protocol, for STEP7-Micro / WIN, V4 |
6ES7 830-2BC00-0YX0 |
WinCC flexible 2004 Micro: Single license on CD-ROM, without authorization:
Engineering software for the configuration of the micro panels OP 73 micro,
and TP 177micro |
6AV6 610-0AA01-0AA0 |
S7-200 PC Access V1.0 (OPC sserver) (Single license) |
6ES7 840-2CC01-0YX0 |
S7-200 PC Access V1.0 (OPC server) (Multi-copy license-15) |
6ES7 840-2CC01-0YX1 |
SIWAREX MS configuration software |
7MH4 930-0AK01 |
SINAUT Micro SC (lincense for 8 stations) |
6NH9910-0AA10-0AA3 |
|
Complete systems |
|
SIMATIC S7-200 entry-level box with CPU222, software STEP7-Micro / WIN,
V4 on CD incl. manual, 1-hour manual, PC / PPI data transmission cable,
simulator, motor module |
6ES7 298-0AA20-0BA3 |
Starter pack OP 73micro (OP 73micro, WinCC flexible Micro,
manual collection on CD-ROM, MPI cable 5 m) |
6AV6 650-0BA01-0AA0 |
Starter pack TP 73micro (TP 73micro, WinCC flexible Micro,
manual collection on CD-ROM, MPI cable 5 m) |
6AV6 650-0DA01-0AA0 |
|
|